8.7/15 Kv Xlpe Insulated Flat Steel Wire Armoured Three Core Cables With Copper Conductor

YXC8VZ3V-R (8.7/15 kV)
medium-voltage-cables-yxc8vz3v-r-8.7-15-kv

YXC8VZ3V-R 8.7/15 kV TS IEC 60502-2

N2XSEYFGbY 8.7/15 kV VDE 0276

  1. Stranded copper conductor
  2. Inner semi-conductive
  3. XLPE insulation
  4. Outer semi - conductive layer
  5. Semi- conductive tape
  6. Copper wire screen
  7. Filler
  8. Seperation sheath
  9. Galvanized flat steel wire
  10. Galvanized steel tape
  11. PVC outer sheath

Technical Data Applications

Maximum operating temp.:90°C

Max.short circuit temp.:250°C (+≥ 5 sn)

Installation temp.min:-5 °C

Standarts: TS IEC 60502 VDE 0276

They are used in cable ducts, outdoor and indoor installations, under ground where the short circuit levels are high and industrial areas fed by electrical also these cables use where there is risk of mechanical damage.

Rated Cross
Section

Overall Diameter
Of Cable

Current Carrying
Capacity

Operating
Inductance

Operating
Capacity

Conductor DC
Resistance at (20 oC)

Net
Weight

Delivery
Lenght

mm2

mm

Air (A)

Ground (A)

mH/Km

µF/Km

Ohm/Km

Kg/Km

Mt

3x25/16

53.00

143

148

0.42

0.15

0.727

4770

500

3x35/16

55.50

173

178

0.40

0.16

0.524

5320

500

3x50/16

59.00

206

210

0.38

0.17

0.387

6130

500

3x70/16

63.00

257

256

0.36

0.19

0.268

7180

500

3x95/16

67.00

313

307

0.34

0.22

0.193

8420

500

3x120/16

71.00

360

349

0.33

0.24

0.153

9630

250

3x150/25

73.50

410

392

0.32

0.26

0.124

10830

250

3x185/25

79.00

469

443

0.30

0.28

0.0991

12800

250

3x240/25

86.50

553

513

0.29

0.31

0.0754

15500

250

3x300/25

90.00

635

576

0.28

0.34

0.0601

17750

250

3x400/35

97.00

731

650

0.27

0.38

0.0470

21420

250