3.6/6 Kv Xple Insulated Single-Core Cables With Copper Conductor

YXC7V-R (3.6/6 kV)
medium-voltage-cables-yxc7v-r-3.6-6-kv

YXC7V-R 3.6/6 kV TS IEC 60502-2

N2XSY 3.6/6 kV VDE 0276

  1. Stranded copper conductor
  2. Inner semi-conductive layer
  3. XLPE insulation
  4. Outer conductive layer
  5. Semi-conductive tape
  6. Copper wire screen
  7. Polyester tape
  8. PVC outer sheath
 

 

Technical Data

Applications

Maximum operating temp.:90°C

Max.short circuit temp.:250°C (+≥ 5 sn)

Installation temp.min:-5 °C

Standarts: TS IEC 60502-2 VDE 0276 

They are used in cable ducts, outdoor and indoor installations, under ground where the short circuit levels are high and industrial areas fed by electrical also these cables use where there is risk of mechanical damage.

Rated Cross
Section

Overall Diameter
Of Cable

Current Carrying
Capacity

Operating
Inductance

Operating
Capaci
ty

Conductor DC
Resistance at (20 oC)

Net
Weight

Delivery
Lenght

mm2

mm

Air (A)

Ground (A)

mH/Km

µF/Km

Ohm/Km

Kg/Km

Mt

1x25/16

18.00

162

166

0.68

0.25

0.727

620

1000

1x35/16

19.50

196

198

0.66

0.28

0.524

710

1000

1x50/16

20.50

235

234

0.63

0.32

0.387

850

1000

1x70/16

22.00

293

286

0.60

0.37

0.268

1060

1000

1x95/16

24.00

358

341

0.58

0.41

0.193

1320

1000

1x120/16

25.00

413

387

0.56

0.46

0.153

1570

1000

1x150/25

26.50

469

431

0.54

0.50

0.124

1930

1000

1x185/25

28.50

537

485

0.53

0.54

0.0991

2290

1000

1x240/25

31.00

633

559

0.51

0.59

0.0754

2850

1000

1x300/25

34.00

722

626

0.49

0.60

0.0601

3470

1000

1x400/35

37.50

826

696

0.47

0.64

0.0470

4440

1000

1x500/35

41.50

943

777

0.46

0.67

0.0366

5490

1000

1x630/35

46.00

1069

860

0.44

0.74

0.0283

6860

1000