YAXC8VZ3V-R 20.3/35 kV TSEK
NA2XSEYFGbY 20.3/35 kV
|
Technical Data | Applications |
Maximum operating temp.:90°C Max.short circuit temp.:250°C (+≥ 5 sn) Installation temp.min:-5 °C Standarts: TS IEC 60502-2 VDE 0276 |
They are used in cable ducts, outdoor and indoor installations, under ground where the short circuit levels are high and industrial areas fed by electrical also these cables use where there is risk of mechanical damage. |
Rated Cross |
Overall Diameter |
Current Carrying |
Operating |
Operating |
Conductor DC |
Net |
Delivery |
|
mm2 |
mm |
Air (A) |
Ground (A) |
mH/Km |
µF/km |
Ohm/Km |
Kg/Km |
Mt |
3x50/16 |
82.00 |
166 |
168 |
0.45 |
0.11 |
0.641 |
9420 |
250 |
3x70/16 |
85.50 |
205 |
205 |
0.42 |
0.12 |
0.443 |
10320 |
250 |
3x95/16 |
90.00 |
249 |
246 |
0.41 |
0.14 |
0.320 |
11370 |
250 |
3x120/16 |
93.50 |
285 |
278 |
0.39 |
0.15 |
0.253 |
12250 |
200 |
3x150/25 |
96.50 |
322 |
311 |
0.37 |
0.16 |
0.206 |
13300 |
200 |
3x185/25 |
101.50 |
369 |
352 |
0.36 |
0.17 |
0.1640 |
14490 |
200 |
3x240/25 |
106.50 |
434 |
408 |
0.34 |
0.18 |
0.1250 |
16170 |
200 |
3x300/25 |
112.50 |
494 |
458 |
0.32 |
0.23 |
0.1000 |
17760 |
200 |
3x400/35 |
119.50 |
569 |
517 |
0.30 |
0.25 |
0.0788 |
19870 |
200 |