  1. Stranded copper conductor
  2. Inner semi condutive layer
  3. XPLE insulation
  4. Outer semi conductive layer
  5. Semi conductive tape
  6. Copper wire screen
  7. Filler
  8. PVC outer sheath

Technical Data Applications

Maximum operating temp.:90°C

Max.short circuit temp.:250°C (+≥ 5 sn)

Installation temp.min:-5 °C

 Standarts: TS IEC 60502-2 VDE 0276

They are used in cable ducts, outdoor and indoor installations, under ground where the short circuit levels are high and industrial areas fed by electrical also These cables use where there is risk of mechanical damage.

Rated Cross
Section

Overall Diameter
Of Cable

Current Carrying
Capacity

Operating
Inductance

Operating
Capacity

Conductor DC
Resistance at (20 oC)

Net
Weight

Delivery
Lenght

mm2

mm

Air (A)

Ground (A)

mH/Km

µF/km

Ohm/Km

Kg/Km

Mt

3x35/16

72.50

182

183

0,48

0,10

0,524

6380

500

3x50/16

75.00

217

214

0,45

0,11

0,387

7080

250

3x70/16

78.50

269

261

0,42

0,12

0,268

8170

250

3x95/16

82.50

326

313

0,41

0,14

0,193

9380

250

3x120/16

86.50

377

356

0,39

0,15

0,153

10630

250

3x150/25

89.00

426

400

0,37

0,16

0,124

11880

250

3x185/25

93.50

488

441

0,36

0,17

0,0991

13660

200

3x240/25

98.50

576

510

0,34

0,18

0,0754

15980

200

3x300/25

104.50

654

604

0,33

0,20

0,0601

18590

200

3x400/35

111.00

754

688

0,31

0,24

0,0470

22240

200