12/20 Kv Xlpe Insulated Flat Steel Wire Armoured Three Core Cables With Copper Conductor

YXC8VZ3V-R (12/20 kV)
medium-voltage-cables-yxc8vz3v-r-12-20-kv

YXC8VZ3V-R 12/20 kV TS IEC 60502-2

N2XSEYFGbY 12/20 kV VDE 0276

  1. Stranded copper conductor
  2. Inner semi-conductive
  3. XLPE insulation
  4. Outer semi - conductive layer
  5. Semi- conductive tape
  6. Copper wire screen
  7. Filler
  8. Seperation sheath
  9. Galvanized flat steel wire
  10. Galvanized steel tape
  11. PVC outer sheath

Technical Data Applications

Maximum operating temp.:90°C

Max.short circuit temp.:250°C (+≥ 5 sn)

Installation temp.min:-5 °C

Standarts: TS IEC 60502-2 VDE 0276

They are used in cable ducts, outdoor and indoor installations, under ground where the short circuit levels are high and industrial areas fed by electrical also these cables use where there is risk of mechanical damage.

Rated Cross
Section

Overall Diameter
Of Cable

Current Carrying
Capacity

Operating
Inductance

Operating
Capacity

Conductor DC
Resistance at (20 oC)

Net
Weight

Delivery
Lenght

mm2

mm

Air (A)

Ground (A)

mH/Km

µF/Km

Ohm/Km

Kg/Km

Mt

3x35/16

60.50

182

183

0,42

0,14

0,524

6060

500

3x50/16

63.50

218

214

0,40

0,16

0,387

6790

500

3x70/16

68.00

271

264

0,38

0,17

0,268

7940

500

3x95/16

72.00

323

313

0,36

0,19

0,193

9230

250

3x120/16

76.00

374

356

0,34

0,21

0,153

10530

250

3x150/25

79.00

419

400

0,33

0,23

0,124

11980

250

3x185/25

84.00

488

452

0,32

0,24

0,0991

13720

250

3x240/25

91.00

579

530

0,31

0,28

0,0754

16460

250

3x300/25

94.50

654

604

0,30

0,30

0,0601

18740

250

3x400/35

102.00

754

688

0,28

0,33

0,0470

22660

250