20.3/35 Kv Xlpe Insulated Flat Steel Wire Armoured Three-Core Cables With Copper Conductor

YXC8VZ3V-R (20.3/35 kV)
medium-voltage-cables-yxc8vz3v-r-20.3-35-kv

YXC8VZ3V-R 20.3/35 kV TSEK

N2XSEYFGbY 20.3/35 kV

  1. Stranded copper conductor
  2. Inner semi-conductive
  3. XLPE insulation
  4. Outer semi - conductive layer
  5. Semi- conductive tape
  6. Copper wire screen
  7. Filler
  8. Seperation sheath
  9. Galvanized flat steel wire
  10. Galvanized steel tape
  11. PVC outer sheath

Technical Data

Applications

Maximum operating temp.:90°C

Max.short circuit temp.:250°C (+≥ 5 sn)

Installation temp.min:-5 °C

Standarts: TS IEC 60502-2 VDE 0276

They are used in cable ducts, outdoor and indoor installations, under ground where the short circuit levels are high and industrial areas fed by electrical also these cables use where there is risk of mechanical damage.

Rated Cross
Section

Overall Diameter
Of Cable

Current Carrying
Capacity

Operating
Inductance

Operating
Capacity

Conductor DC
Resistance at (20 oC)

Net
Weight

Delivery
Lenght

mm2

mm

Air (A)

Ground (A)

mH/Km

µF/km

Ohm/Km

Kg/Km

Mt

3x35/16

80.00

182

182

0,47

0,10

0,524

8750

250

3x50/16

82.00

217

214

0,46

0,11

0,387

9550

250

3x70/16

86.50

269

261

0,44

0,12

0,268

10800

250

3x95/16

90.50

326

313

0,42

0,14

0,193

12200

250

3x120/16

94.40

377

356

0,39

0,15

0,153

13500

200

3x150/25

97.40

426

400

0,37

0,16

0,124

15050

200

3x185/25

102.00

510

441

0,36

0,17

0,0991

16900

200

3x240/25

108.50

579

510

0,34

0,18

0,0754

19550

200

3x300/25

113.00

654

604

0,32

0,23

0,0601

22400

200

3x400/35

120.30

754

688

0,31

0,25

0,0470

26600

200