12/20 Kv Xlpe Insulated Single Core Cables With Copper Conductor

YXC7V-R (12/20 kV)
medium-voltage-cables-yxc7v-r-12-20-kv

YXC7V-R 12/20 kV TS IEC 60502-2

N2XSY 12/20 kV VDE 0276

 

  1. Stranded copper conductor
  2. Inner semi-conductive layer
  3. XLPE insulation
  4. Outer conductive layer
  5. Semi-conductive tape
  6. Copper wire screen
  7. Polyester tape
  8. PVC outer sheath

Technical Data Applications

Maximum operating temp.:90°C

Max.short circuit temp.:250°C (+≥ 5 sn)

Installation temp.min:-5 °C

Standarts: TS IEC 60502-2 VDE 0276

They are used in cable ducts, outdoor and indoor installations, under ground where the short circuit levels are high and industrial areas fed by electrical also these cables use where there is risk of mechanical damage.

Rated Cross
Section

Overall Diameter
Of Cable

Current Carrying
Capacity

Operating
Inductance

Operating
Capacity

Conductor DC
Resistance at (20 oC)

Net
Weight

Delivery
Lenght

mm2

mm

Air (A)

Ground (A)

mH/Km

µF/Km

Ohm/Km

Kg/Km

Mt

1x25/16

24.00

169

165

0.69

0.14

0.727

800

1000

1x35/16

25.50

204

197

0.67

0.16

0.524

920

1000

1x50/16

26.50

244

233

0.64

0.17

0.387

1070

1000

1x70/16

28.50

303

284

0.61

0.20

0.268

1310

1000

1x95/16

30.00

368

340

0.59

0.22

0.193

1590

1000

1x120/16

32.00

424

386

0.57

0.24

0.153

1860

1000

1x150/25

33.00

479

431

0.55

0.26

0.124

2230

1000

1x185/25

35.00

548

485

0.53

0.28

0.0991

2620

1000

1x240/25

37.50

643

559

0.51

0.31

0.0754

3200

1000

1x300/25

40.00

731

626

0.50

0.34

0.0601

3820

1000

1x400/35

43.00

834

699

0.48

0.38

0.0470

4800

1000

1x500/35

46.50

955

782

0.46

0.41

0.0366

5850

1000

1x630/35

51.00

1084

869

0.46

0.46

0.0283

7230

1000