20.3/35 Kv Halogen Free Flame Retardant Xlpe Insulated Single-Core Cables With Copper Conductor

N2XSH (20.3/35 kV)
medium-voltage-cables-n2xsh-20.3-35-kv

N2XSH 20.3/35 kV TSEK

  1. Stranded copper conductor
  2. Inner semi condutive layer
  3. XPLE insulation
  4. Outer semi conductive layer
  5. Semi conductive tape
  6. Copper wire screen
  7. Polyester tape
  8. HFFR outer sheath

Technical Data Applications

Maximum operating temp.:90°C

Max.short circuit temp.:250°C (+≥ 5 sn)

Installation temp.min:-20 °C

Standarts: TS IEC 60502-2 VDE 0276 

They are used in cable ducts, outdoor and indoor installations, under ground where the short circuit levels are high and industrial areas fed by electrical also these cables use where there is risk of mechanical damage.

Rated Cross
Section

Overall Diameter
Of Cable

Current Carrying
Capacity

Operating
Inductance

Operating
Capacity

Conductor DC
Resistance at (20 oC)

Net
Weight

Delivery
Lenght

mm2

mm

Air (A)

Ground (A)

mH/Km

µF/Km

Ohm/Km

Kg/Km

Mt

1x35/16

33.00

169

165

0,69

0,12

0,524

1285

1000

1x50/16

35.00

249

232

0,66

0,13

0,387

1460

1000

1x70/16

36.00

308

284

0,63

0,14

0,268

1710

1000

1x95/16

38.00

375

339

0,60

0,15

0,193

2025

1000

1x120/16

40.00

430

385

0,59

0,17

0,153

2300

1000

1x150/25

41.00

485

430

0,57

0,18

0,124

2705

1000

1x185/25

43.00

554

484

0,55

0,19

0,0991

3100

1000

1x240/25

45.00

653

559

0,53

0,21

0,0754

3700

1000

1x300/25

48.00

739

627

0,51

0,23

0,0601

4360

1000

1x400/35

52.00

842

701

0,49

0,25

0,0470

5400

500

1x500/35

55.00

965

786

0,48

0,27

0,0366

6485

500

1x630/35

60.00

1096

875

0,46

0,30

0,0283

7950

500